TCM/25-E ( Integrated primary bar )


General data

Rated short-time thermal current (LTH)

100/1 In/s
Max 40 kA

Insulation levels

36/70/170 kV (r.m.s.)

Rated frequency

50 ÷ 60 Hz

Primary current

100 ÷ 1000 A

Rated secondary current

5 or 1 A

Working temperature

-50 ÷ +80 °C

Storage temperature

-50 ÷ +80 °C

Protection degree

IP65

Approximate weight

20 kg


  • Acording to IEC 60044-1
  • Acording to IEC 61869-2
  • Silicone insulated
  • Partial discharge free
  • Other executions on request
  • For outdoor use

Others ratios and accuracy classes on request

S.T.E. Strumenti Trasformatori Elettrici S.r.l.
Via Camillo Benso Conte di Cavour 66, 20865 Usmate Velate (MB), Italy
+39 (039) 68.29.450   +39 (039) 68.29.455   ste@stesrl.it
P.IVA: 00821070968 • C.F: 06271510155
Cap. soc. 110.000 € i.v. - Tribunale di Monza 21325 - REA 1086796

STE

           

On this site we use cookies, including those of third parties, anonymously in order to improve our services. For more information or to find out how to block Cookies, see our information.