TC 63 ( Ø inn. 63 mm )
General data
Rated short-time thermal current (LTH)
100/1 In/s
Max 40 kA
Insulation levels
0.72/3 kV (r.m.s.)
Rated frequency
50 ÷ 60 Hz
Primary current
400 ÷ 1500 A
Rated secondary current
5 - 1 A
Approximate weight
1 Kg
Protection degree
IP20
Working temperature
-10 ÷ +70 °C
Storage temperature
-20 ÷ +80 °C
Class on request
5P5 / 5P10 / 0,2 / 0,2 S
- Acording to IEC 60044-1 standards
- Acording to IEC 61869-2 standards
- Dry insulation
- Self-extinguishing plastic case
- Wall mounting pins
- Laser marked rating plate on the case, on request
- Other ratios on request
- Indoor use
Available wiht UTF sealable terminal cover